3M Bair Paws 875 Series

Preventive Maintenance Procedure

On this page

Asset Type

Patient Warming System

Manufacturer

3M

Model

Bair Paws 875 Series

Manual Reference

3M Bair Paws Model 875 Warming Unit Service Manual, document/reorder number 202036A, May 2013. Confirm the current manufacturer revision before use.

Manufacturer Recommendation / AEM Status

The manufacturer lists operating-temperature calibration and over-temperature circuit testing every 6 months. Calibration is also required after service procedures. Replace the filter every 6 months or sooner if necessary, clean as needed, and inspect for damage before each use.

Calibration requires the Model 90055 Temperature Test Kit and a calibrated K-type thermocouple thermometer. The steady-state calibration target is 43.0°C +/-0.5°C; do not calibrate above 43°C.

During the over-temperature test, the Over-Temp indicator must illuminate, the audible alarm must sound, the heater must switch off within 2 minutes, and peak test-kit temperature must remain below 56°C. The OT threshold is not adjustable.

After repairs and before return to service, the manufacturer safety inspection includes operating-temperature calibration, OT detection testing, leakage-current testing, and safety-ground continuity testing.

If a facility changes the listed activities or interval, that should be handled under its approved AEM program, risk assessment, maintenance history, and applicable regulatory requirements.

What This PM Procedure Covers

Required Tools and Equipment

Step-by-Step PM Procedure

1. Identify and Prepare the Unit

Action: Verify asset and serial numbers, Model 875 identity, voltage rating, location, service history, and current manual revision. Remove the unit from patient use, disconnect the disposable gown, turn the controller off, and unplug it.

Expected outcome: The correct unit is confirmed and safe to inspect.

2. Inspect the Warming Unit

Action: Inspect enclosure, labels, inlet/outlet, hose and couplers, controller and cord, holder, mounting clip, case bottom, fasteners, power cord, plug, ground pin, cord retainer, and equipotential connection for damage, blockage, contamination, fluid intrusion, exposed conductors, or overheating.

Expected outcome: Components are intact, legible, secure, cleanable, and unobstructed.

3. Inspect the Mounting Arrangement

Action: Verify placement on a flat hard surface or secure attachment to the applicable wall, pole, suction-wall, or rail mount. Confirm full seating and secure hardware; a bedrail mount requires its safety strap. For an IV pole, use no higher than 44 inches (112 cm) with a minimum 14-inch (35.6 cm) wheelbase radius.

Expected outcome: The installation is stable and does not block the air intake.

4. Clean the Unit

Action: With power disconnected, wipe the cabinet, controller, and hose exterior with a damp soft cloth and mild solution or antimicrobial spray. Dry separately. Do not immerse components, use a dripping-wet cloth, or use harsh solvents.

Expected outcome: Surfaces are clean, dry, and undamaged.

5. Replace the Filter

Action: Disconnect power. Remove the two dark-purple case-bottom screws, slide the bottom down the hose, replace the filter, then restore the bottom and both screws.

Expected outcome: A clean manufacturer replacement filter is correctly installed and secured.

6. Set Up the Temperature Test

Action: Test in an environment similar to clinical use and within 18-26°C (65-79°F). Connect the hose to the Model 90055 kit, insert the thermocouple through its grommet, center the tip in the test-kit cross section, and extend the hose straight to full length.

Expected outcome: The approved test kit and calibrated thermometer are correctly positioned.

7. Warm the System

Action: Turn the controller fully clockwise to maximum airflow and temperature and warm for 10 minutes. Keep it at maximum during calibration.

Expected outcome: The unit reaches a stable test condition.

8. Calibrate Operating Temperature

Action: Slide the case bottom down the hose to access calibration. Insert the 2-mm screwdriver about one-half inch into the access hole. Turn the potentiometer very slowly until 43°C, then wait at least 5 minutes for steady state.

Expected outcome: Temperature stabilizes at 43.0°C +/-0.5°C. Never calibrate above 43°C.

9. Test the Over-Temperature Circuit

Action: Using a small screwdriver, continuously press the OT test button while monitoring temperature and heater-shutdown time. The test drives the heater full-on and unregulated.

Expected outcome: The OT indicator illuminates, the audible alarm sounds, the heater shuts off within 2 minutes, and peak temperature remains below 56°C.

Failure action: Release the button, turn the controller off, unplug the unit, remove it from service, and contact authorized support. Do not adjust the OT threshold.

10. Reset and Confirm Cool-Down

Action: Turn the controller off, wait 10 seconds, then select the low setting. After several minutes, verify temperature approaches ambient.

Expected outcome: The alarm resets and the unit cools normally without a fault.

11. Reassemble and Function-Test

Action: Restore the case bottom, filter, and both screws without pinching the hose or controller cord. Turn the dial through its range and verify low-setting click-on, increasing airflow and temperature, and absence of abnormal noise, odor, restriction, fault, or shutdown.

Expected outcome: The unit is correctly assembled and operates normally across its range.

12. Perform Electrical Safety Testing

Action: Test protective-earth resistance and touch/chassis leakage using the facility's Class I, Type BF procedure. These tests are specifically included after repair.

Expected outcome: Results meet applicable facility limits.

13. Final Inspection and Documentation

Action: Disconnect the test kit. Confirm a clear air path, secure hose/controller, installed filter/covers, clean dry surfaces, and no alarm or fault. Apply the PM label and document all results.

Expected outcome: The unit is complete, within specification, and ready for service.

Electrical Safety Testing

The Model 875 is Class I, Type BF equipment. The manual states that leakage meets IEC 60601-1 and UL 60601-1 requirements but does not give a universal field limit.

Ground resistance measured in ohms, expected ≤ 0.5 Ω or facility/NFPA 99 criteria if different.

Touch/chassis leakage measured in microamps:
Facility limit used =
Result =
Pass / Fail =

Pass / Fail Criteria

PM Pass Criteria

Remove From Service Criteria

Copy/Paste CMMS Work Order Procedure

Use the manufacturer service manual, facility policy, and approved AEM program to determine the final PM interval and return-to-service requirements.

Sources Used

Was this PM procedure helpful?

Don't see a guide you need?

Suggest a Guide